previous
  • 7 Small Bathroom Layouts
    7 Small Bathroom Layouts
  • 7 Trim Carpentry Secrets
    7 Trim Carpentry Secrets
  • Energy-Smart Details
    Energy-Smart Details
  • Magazine Departments
    Magazine Departments
  • Classic Cabinets
    Classic Cabinets
  • Read FHB on Your iPad
    Read FHB on Your iPad
  • Clever daily tip in your inbox
    Clever daily tip in your inbox
  • 9 Concrete Countertops Ideas
    9 Concrete Countertops Ideas
  • Tips & Techniques for Painting
    Tips & Techniques for Painting
  • Video: Install a Fence
    Video: Install a Fence
  • Video Series: Tile a Bathroom
    Video Series: Tile a Bathroom
  • Hot Water Now
    Hot Water Now
  • Custom Flooring Inspiration
    Custom Flooring Inspiration
  • Pro Tool Rental. Learn More.
    Pro Tool Rental. Learn More.
  • Radiant Heat Comparison
    Radiant Heat Comparison
  • Basement Remodeling Tips
    Basement Remodeling Tips
  • Design Inspiration
    Design Inspiration
  • Remodeling Articles
    Remodeling Articles
  • All about Roofing
    All about Roofing
  • Master Carpenter Videos
    Master Carpenter Videos
  • 7 Smart Kitchen Solutions
    7 Smart Kitchen Solutions
next

Outlets in brick walls

Q:

I live in an old house and want to install outlets in the baseboards of a second-floor bedroom that has no power. I already ran a 20-amp home run from the electrical panel to one corner of the room, but I can’t run wires through two of the stud walls because they’re infilled with brick. Can I run armor-clad (AC) wire behind the baseboard and staple it to the face of the studs?






A:

Brian Walo, a licensed electrician in Mount Pleasant, S.C., replies: Running AC or nonmetal clad (NMC) cable behind the baseboards is fine provided that the "protection from physical damage" requirement outlined in Article 300.4 of the National Electrical Code (NEC) is followed explicitly. Essentially, the section states that for an application such as this one, you must eliminate the possibility that an errant nail or screw will hit the cable while you're reinstalling baseboard or other finish material.

Although AC cable is approved for exposed work, where it won't be subject to physical damage, the shielding on AC cable does not provide sufficient protection from nails when it is concealed in a wall or behind baseboard. Therefore, like NMC cable, if it's within 11/4 in. of the finished surface, it must be protected by at least 1/16-in.-thick steel plating.

The simplest approach in the walls that aren't brick-filled is to remove the baseboard and drill holes through the studs as you normally would. It's also possible to notch the studs as long as you comply with local code requirements. Whether you drill holes or notch studs, you need to install an approved nail plate over each location where the cable passes through the studs within 11/4 in. of the finished surface.

For brick walls, I've often used rigid wire mold, which remains exposed and feeds specially designed outlet boxes that are left exposed as well. If you're set on keeping the cable behind the baseboard, your options are limited. You could attach the cable to the studs, then fur them to clear the cable. If you do that, make sure to size the furring so that the finished face of the baseboard will be at least 11/4 in. from the cable. Otherwise, you need to conceal it within metal conduit.



From Fine Homebuilding 201, pp. 88 January 14, 2009