Hazard-Free Hot Tubs
The electrical hookup is only one part of the equation; when installing a hot tub, there are a number of key requirements to keep in mind.
Installing a self-contained hot tub involves more than just an electrical hookup; it requires careful adherence to multiple building and electrical codes. Key considerations include maintaining proper distances from windows, outlets, and overhead power lines, as well as ensuring safety glazing near wet areas.
Additionally, equipotential bonding is critical to prevent electrical hazards. This article provides an overview of these regulations, helping landscape designers, deck builders, and DIY homeowners plan hot tub installations safely and in compliance with code.
Code Considerations for a Hot Tub
Whether you plop it down on a simple prefabricated pad outside your back door or incorporate it into a six-figure luxury backyard remodel, installing a self-contained hot tub is often thought of as nothing more than an electrical hookup. There are plenty of requirements in the National Electrical Code (NEC) related to conductor sizing, grounding, overcurrent protection, GFCI protection, disconnecting means, and, of course, having enough space in your panel for the new circuit.
It’s the perfect job for a licensed electrician knowledgeable in the NEC. But before the electrician arrives, there’s an assortment of other electrical and building codes related to where the hot tub will be located in relation to the house and other features commonly found in backyards.
These life-safety requirements are often overlooked when planning hot tub locations, and the solutions to address these issues without a complete redesign are rarely ideal. Landscape designers, deck builders, and DIY homeowners: This article is for you, not your electrician. All the codes for hot tubs are scattered across multiple chapters and code books.
Though the NEC is the origin of the electrical codes discussed here, they are also provided in the International Residential Code (IRC). The IRC, however, references the International Swimming Pool and Spa Code (ISPSC) for a few more requirements. I’ve provided the relevant code sections, and both codes can be read online at no charge at codes.iccsafe.org.
Safety Glass
Hot tubs are wet, and so is the area around them. Wet means slippery, and slippery is more hazardous when there’s glazing (glass) nearby. All glass within 5 ft. horizontally from the edge of the water (the inside walls of the tub) and less than 60 in. vertically above a standing or walking surface must be safety-glazed.
This applies to both the surface inside the hot tub and the surfaces outside, such as a deck or patio, when within the 5-ft. horizontal distance. Since this requirement relates to falling toward the glass, the horizontal distance is measured in straight lines, not around corners.
Tempered glass is a popular choice for safety glazing, but there are also window security films available that have been tested to meet the safety-glazing standards referenced in the IRC (R324.4.5; these codes are found in section R308 in previous editions). It is not uncommon to see hot tubs hazardously placed adjacent to the existing windows of a house. The safest design is to keep them 5 ft. away.
Switches, Disconnects, and Outlets
Electrical switches must also be at least 5 ft. horizontally from the edge of the water, unless they are listed (tested) for closer proximity (E4203.2). This distance is measured along the most direct path, which doesn’t necessarily have to be straight. The goal is to reduce the hazard by minimizing the ease of reaching the switch while in the tub, accounting for the possibility that you could reach around a corner.
The electrical service to the hot tub must have a disconnecting means, and a circuit breaker can serve this purpose. The electrician installing the hot tub will handle the actual installation, but owners should think ahead about the location of the disconnect during the design process. If the circuit breaker is too far from the hot tub to meet the NEC’s proximity requirements, a separate switch in an enclosure may be necessary.
While many homeowners may not want an unsightly metal electrical box visible from their hot tub, the NEC requires its placement for safety reasons. The disconnecting means protects someone who is servicing the hot tub, allowing them to disconnect all power. They need to be able to see the disconnect while at the tub, and for the person at the disconnect to see them, to ensure the power remains off.
For this reason, E4203.3 requires the disconnecting means to be at least 5 ft. away, to protect the occupant, but also “within sight” of the hot tub, to protect the service personnel. Per the definition of the phrase “in sight” in chapter 35 of the IRC, this also means not more than 50 ft. away.
Receptacle Outlets
Receptacle outlets must also be kept a safe distance from tub water, due to the potential reach of cords and plugged-in devices. The average cord length for a household appliance is generally no more than 6 ft. long; therefore, receptacle outlets must be at least 6 ft. from the edge of the water. As with switches, the measurement is taken in the shortest path an appliance cord can travel without passing through any door or window openings.
Any receptacles within 20 ft. horizontally from the inside edge of the tub must be GFCI protected. (In fact, this is a requirement for all outdoor receptacles.) As with disconnects, someone working on the hot tub is also afforded consideration. At least one receptacle must be provided within 20 ft. of the water’s edge. This minimizes the use of extension cords and the hazards they create during service work (E4203.1).
Lighting, Fans, and More
Other common electrical features found in backyards and under patio covers are luminaires (lights) and ceiling fans. Again to minimize the risk of electrical hazards, these items cannot be located above a hot tub or within 5 ft. horizontally from the water’s edge, unless they are at least 12 ft. above the maximum water level (E4203.4.1).
Where located between 5 ft. and 10 ft. horizontally from the water, these features must be GFCI protected, unless rigidly attached to a structure and at least 5 ft. above the maximum water level (E4203.4.6). When installing a new hot tub near existing lights and fans, in the region 5 ft. horizontally outside of the tub, the minimum 12-ft. height can be reduced to a minimum of 5 ft. above the maximum water level where the outlet and the luminaire are rigidly attached to the existing structure and GFCI protected. They still must be at least 12 ft. above when directly over the hot tub (E4203.4.4). Other electrical outlets for items such as fire alarms must be at least 10 ft. from the inside walls (E4203.5).
Don’t Forget to Look Up
So far, keeping a hot tub at least 6 ft. from the side of a house is an easy way to avoid having to remember all these details. Now it’s time to look overhead. Overhead electrical service cables are another hazard we don’t want to mix with our hot tubs. A hot tub cannot be located underneath any overhead service conductor or any other open wiring anywhere within a 10-ft. horizontal distance from the water’s edge.
There is an exception when the distance from the water to the conductor is greater than 22-1⁄2 ft. to 27 ft. depending on variables better suited for your electrician to evaluate. The main takeaway here is to stay at least 10 ft. away horizontally from overhead conductors (E4203.7).
Equipotential Bonding
Voltage represents the difference of electrical potential between two points. The bigger the difference, the bigger the voltage and the bigger the hazard. Just like heat moves to cold and moist moves to dry, so does high electrical potential move to low potential.
We face electrical hazards when we become the path for current flowing from high to low potential. Surprising as it may be to many, the earth has electrical potential of varying degrees at varying times and places. It can have voltage. Dirt, concrete, and even a hot tub itself can become energized.
When you are in the water, you share the water’s electrical potential; similar to a bird on a wire, you aren’t a path for that electrical charge to move to an item of lesser electrical potential. However, when you swing a leg out of the water and place it down outside the tub with the other still inside, you’ve made a connection and become a conductor.
Regardless of which surface has the greater charge at any given time or place, the concern is any current moving through you. This is why the NEC requires equipotential bonding, a safety practice that involves connecting all exposed conductive parts of electrical equipment and nearby metal objects. This keeps everything you might touch while in the water under the same electrical potential; thus, there is no voltage for you to experience.
The wires connecting these items together do not have to be grounded back to the service panel for any overcurrent or GFCI protection. They simply connect everything you touch together electrically so there is no current. I’ll cover some key points about this subject, but you should consult your electrician for specific implementation.
More to Consider
Metal guardrails, doors, window frames, awnings, and other similar features might have a different electrical potential than you and the water, so in line with other clearances related to reach, if fixed metal objects are within 5 ft. horizontally of the water’s edge and less than 12 ft. above the water, they must be bonded together with the tub and possibly the perimeter surface.
Perimeter surface equipotential bonding includes bonding to the reinforcing steel in a surrounding concrete slab or burying a copper wire or grid below the surrounding ground or paving. It applies to “unpaved surfaces, concrete, and other paving,” and there are various interpretations about what this includes. While I have heard of inspectors requiring this bonding on elevated wood decks, I do not believe this is the common interpretation.
There is one clear exception for perimeter surface bonding specific to listed, above-grade, outdoor, “self-contained” hot tubs. (This is essentially your common “plug and play” hot tub.) When the perimeter surface around the hot tub within a horizontal distance of 30 in. from the tub is more than a 28-in. vertical distance from the top rim, equipotential perimeter surface bonding is not required of any surface type. Otherwise, it’s time for a discussion with your electrician and electrical inspector (E4204.2).
One Big Dead Load
The weight of all construction materials and permanent equipment on a structural assembly—like a backyard deck—creates what we call dead loads. And a tub full of hundreds of gallons of water adds a significant dead load. When using pre-engineered span tables for designing a deck’s structural members, like joists and beams, you must ensure the tables’ dead- and live-load assumptions match your needs, as these form the basis of the engineering calculations.
Commonly, span tables are provided for 10-psf and 20-psf uniformly distributed dead loads. In every circumstance—even a kiddie pool—the weight of the water will exceed 20 psf. For lower-level decks, it’s ideal to support the tub directly on grade and build the deck around it, avoiding the need for specific engineering of the deck structure.
If the tub is going to sit on the deck, you’ll need an engineered design to support the loads. This applies not just to joists but to the whole load path to the earth—the beams, ledger, posts, hardware, and piers. Guesswork isn’t an option; beyond the weight of the water in the tub, you must account for the live load of a concentrated group of people (R301.1).
Providing Access
Hot-tub pumps must have sufficient clearance for repair and replacement. This mess of plumbing equipment, as well as terminations of the electrical feeders providing the power to the tub, is housed and concealed within the tub shell. Access to these components is important, and in the case of a sunken or partially sunken tub, it requires a little bit of attention.
Tub access requirements will vary with each manufacturer and model. Some tubs require access from more than one side of the shell, and others require that you access only a small panel for the feeder terminations, as the pumps are accessed from the wet side of the tub, behind each jet.
Unless there is clearance on all sides in the designed location, the details of the tub’s design and access points should be known in advance. The NEC requires minimum clearances for “energized equipment,” and that term is interpreted differently by different professionals. The default best choice is to provide the minimum service clearance space of 30 in. wide, 36 in. deep, and 6 ft. 6 in. tall (E3405.2).
International Swimming Pool and Spa Code
Section R328 of the 2024 IRC is a single sentence: “The design and construction of pools and spas shall comply with the International Swimming Pool and Spa Code.” Section 306 of this code provides additional requirements for decks serving hot tubs, regarding slip resistance of the surface and sloping or gapping the decking for drainage. These code sections are not as commonly adopted or enforced across the U.S. as the previous ones, but they still contain good advice to employ by choice.
Section 305 of this code is about required barriers to prevent small children from entering the pool. These life-safety requirements are commonly expected, and more than a good idea. Check out Know the Code in FHB #310 (“Barriers to pool entry”) for all the details about these barrier codes.
Clearly there’s more to consider when installing a new hot tub than just wiring it up correctly. Whether you’re setting one down on your back patio or designing a client’s backyard retreat, proper planning ensures that everyone can safely enjoy the soothing bubbles.
Code CheckThis column references the model 2024 International Residential Code and provides section number references to that edition. State and local governments often make amendments to the model IRC at adoption, so always verify the adopted and amended code edition as administered by your building authority. |
— Glenn Mathewson; consultant and educator with BuildingCodeCollege.com.